1.SummaryZW32-12 series High Voltage vacuum breaker is a kind of outdoor voltage switch equipment with 50HZ three-phase alternating current and 12KV rated voltage.It apply to breaker and close the loa...

1.Summary
ZW32-12 series High Voltage vacuum breaker is a kind of outdoor voltage switch equipment with 50HZ three-phase alternating current and 12KV rated voltage.It apply to breaker and close the load current,overload current and short-circuit current in cities or country power distribution system.
2.Service Environment
·The height above sea level is not greater than 2000m;
·The ambient temperature upper limit is +45 ℃, lower limit -30℃;
·The wind pressure does not exceed 700Pa(wind speed 34m/s) ;
·There is no regular violent vibrations;
·Dirtiness class: Ⅲ class;·
3.Rated technical parameter of the breaker:


Project

Unit

Data

Rated voltage

kV

11

Rated current

A

630

Rated short-circuit breaking current

kA

20

Rated closing current ( Peak value)

50

Rated peak withstand current

50

Rated short time withstand current

20

Rated short-circuit keeping time

s

4

Rated frequency

Hz

50

Rated Insulating level

Lightning impulse withstand voltage test (Peak value)

kV

75

1min power frequency withstand voltage

42

Rated operate sequence

 

O--0.3s--CO--180s--CO

Rated Short-circuit Current On and Off Times

Times

30

Mechanical life-span

10000

Rated working voltage (closing and switch-off coil)

V

AC220

Permit abrasion total thickness of active and static contactor

mm

3

Rated current of release over-current

A

5

Current ratio of the current transformer

 

200/5,400/5,630/5,

Contactor torque

mm

9±1

Contactor over-travel

2±0.5

Average speed of breaking brake

m/s

1.2±0.2

Average speed of closing brake

0.6±0.2

Times of breaking brake

ms

20~60

Times of closing brake

20~55

Bounce time of closing brake

≤2

Three-phase breaking or closing simultaneity

≤2

Loop direct current resistance of each phase

≤80

Power storage electric motor

Rated voltage

V

DC/AC 220

Rated power

W

70

Power storage time

s

≤8

Quality

kg

85

4. External dimension and installation
4.1 External dimension and installation size (mm)


4.2 The installation drawing of the single pole-mounted